全自动高效水-水换热机组2
产品简介
详细信息
全自动高效水-水换热机组
高效湍流板式换热机组选型参数明细表
机组型号 | 供热量 MW | 采暖面积 万m² | 二次循环水量 t/h | 一次额定水量 t/h | 循环泵 | 补水泵 | 外形尺寸 长×宽×高(m) | ||||
型号 | 功率 KW | 台数 | 型号 | 功率 KW | 台数 | ||||||
SDSU-N-0.35 | 0.35 | 0.5 | 15 | 12 | 65-140 | 3 | 2 | 20-160 | 1.1 | 2 | 2.8×1.2×1.6 |
SDSU-N-0.7 | 0.7 | 1.0 | 30 | 24 | 65-150 | 4 | 2 | 25-160 | 1.5 | 2 | 2.8×1.2×1.6 |
SDSU-N-1.05 | 1.05 | 1.5 | 45 | 36 | 80-140 | 5.5 | 2 | 25-160 | 1.5 | 2 | 2.8×1.2×1.6 |
SDSU-N-1.4 | 1.4 | 2.0 | 60 | 48 | 80-150 | 7.5 | 2 | 40-160 | 2.2 | 2 | 3.0×1.5×1.9 |
SDSU-N-1.75 | 1.75 | 2.5 | 75 | 60 | 100-150 | 11 | 2 | 40-160 | 2.2 | 2 | 3.0×1.5×1.9 |
SDSU-N-2.1 | 2.1 | 3.0 | 90 | 72 | 100-50 | 11 | 2 | 40-160 | 2.2 | 2 | 3.0×1.5×1.9 |
SDSU-N-2.8 | 2.8 | 4.0 | 120 | 96 | 100-160 | 15 | 2 | 50-160 | 3 | 2 | 3.8×1.6×2.1 |
SDSU-N-3.5 | 3.5 | 5.0 | 150 | 120 | 125-150 | 18.5 | 2 | 50-160 | 3 | 2 | 3.8×1.6×2.1 |
SDSU-N-4.2 | 4.2 | 6.0 | 180 | 144 | 150-300 | 22 | 2 | 50-160 | 3 | 2 | 3.8×1.6×2.1 |
SDSU-N-4.9 | 4.9 | 7.0 | 210 | 168 | 150-300 | 22 | 2 | 65-170 | 5.5 | 2 | 3.8×1.6×2.1 |
SDSU-N-5.6 | 5.6 | 8.0 | 240 | 192 | 150-315 | 30 | 2 | 65-170 | 5.5 | 2 | 3.8×1.6×2.1 |
SDSU-N-6.3 | 6.3 | 9.0 | 270 | 216 | 125-150 | 18.5 | 3 | 65-170 | 5.5 | 2 | 4.5×2.0×2.4 |
SDSU-N-7.0 | 7.0 | 10 | 300 | 240 | 125-150 | 18.5 | 3 | 65-170 | 5.5 | 2 | 4.5×2.0×2.4 |
SDSU-N-8.4 | 8.4 | 12 | 360 | 288 | 150-300 | 22 | 3 | 65-170 | 5.5 | 2 | 5.0×2.2×2.5 |
SDSU-N-9.8 | 9.8 | 14 | 420 | 336 | 150-300 | 22 | 3 | 65-170 | 5.5 | 2 | 5.0×2.2×2.5 |
SDSU-N-11.2 | 11.2 | 16 | 480 | 384 | 150-315 | 30 | 3 | 80-170 | 7.5 | 2 | 5.0×2.2×2.5 |
SDSU-N-12.6 | 12.6 | 18 | 540 | 432 | 200-300 | 37 | 3 | 80-170 | 7.5 | 2 | 5.5×2.5×2.8 |
SDSU-N-14.0 | 14.0 | 20 | 600 | 480 | 200-300 | 37 | 3 | 80-170 | 7.5 | 2 | 5.5×2.5×2.8 |
SDSU-N-17.5 | 17.5 | 25 | 750 | 600 | 250-300 | 55 | 3 | 100-160 | 11 | 2 | 6.2×2.5×2.8 |
SDSU-N-21.0 | 21.0 | 30 | 900 | 720 | 250-300 | 55 | 3 | 100-160 | 11 | 2 | 6.2×2.5×2.8 |
也可根据用户实际工况另行设计;
2.性能参数中供暖热指标按q=70W/㎡计算,若有不同,请注意修正;配备3台循环泵时,为2台运行1台备用;
3.由于篇幅所限,本机组性能参数未一一列出,具体工程可按本机组性能参数表进行修正,或与我公司联系,公司可根据用户需要另行设计。